Rackmount Inverter - 2U, 1600 & 2400 W
Elevate Your Power Solutions
Introducing the Rackmount Inverter Series—a pinnacle of reliability, performance, and innovation tailored for critical power applications. Engineered for efficiency and versatility, our inverters are designed to meet the rigorous demands of the LMR, Broadband, and WISP industries.
These 2U, 1600 & 2400 W true-sine wave inverters are designed to provide seamless 120 VAC 50/60 Hz back-up power for AC powered communications equipment from the site’s 48 or 125 VDC power system. Ensure equipment operation remains uninterrupted in the event of a power grid failure or if the site utility power is disconnected for maintenance or upgrade purposes.
Features
- 19" Rack Mount 2U Design: Compact and efficient, fitting seamlessly into standard racks for optimal space utilization.
- Pure Sine Wave Operation: Delivers clean and stable power, ensuring compatibility with sensitive electronics and minimizing harmonic distortion.
- Alarm Contacts: Provides versatile alarm notifications for enhanced system management.
- Black Chassis: Sleek and professional appearance that blends with most equipment racks.
- AC Bypass Switch with 4x Receptacles: Ensures uninterrupted power with easy bypass functionality
- Display: User-friendly control and operation interface with real-time display for monitoring performance.
- Design Compliance: Built in accordance with Newmar’s standard design practices for reliability and consistency.
REQUEST MORE INFORMATION:
Comparison with Existing Solutions
Target Audience
Land Mobile Radio
(LMR)
Ensures reliable power for communication systems in critical environments.
Broadband
Providers
Delivers stable and efficient power for broadband infrastructure, maintaining connectivity and performance.
Wireless Internet
Service Providers
Supports robust power needs for wireless communication networks, enhancing service reliability.
Electrical Specifications
Model | 1600 W Options | 2400 W Option |
---|---|---|
Rating | 2000 kVA | 3000 kVA |
DC Input | ||
Nominal Voltage/ Max. Current |
48 VDC/50 Amps |
125 VDC/20 Amps |
Voltage Range |
48 VDC [42~64 VDC] |
125 VDC [105~160 VDC] |
Efficiency | >85% (full load) at 48 or 125 VDC | |
AC Input (Bypass) | 2000 kVA | 3000 kVA |
Nominal Voltage | 110 or 230 VAC ±25% | |
Frequency | 50 or 60 Hz ±3 Hz | |
Protection | AC Circuit Breaker | |
Inverter Output | ||
Output Power | 1600 W | 2400 W |
Max. Surge Power | 2400 W | 3600 W |
Voltage | 100 or 230 VAC ±1% | |
Voltage Regulation | <2% at linear load | |
Frequency | 50 or 60 Hz ±0.1% | |
THD Distortion | <3% at linear road | |
Waveform | Pure Sine Wave | |
Crest Power | 3:1 | |
Protection | ||
Short Circuit | Inverter shut-off | |
Overload | 105~125% for 60 s; 126~150% for 30 s; >151% for 1s; Transfer to bypass | |
DC Polarity Reverse | Yes | |
Communication | RS-232 or dry contact |
Mechanical Specifications
Model | 1600 W Options | 2400 W Option |
---|---|---|
Dimensions (L x W x H) | 488 x 430 x 89 mm [19”x 16.9 x 3.5”] [2U] | |
Weight | 12.0 kg (26.5 lb) |
Environmental
Model | 1600 W Options | 2400 W Option |
---|---|---|
Temperature | 0–40ºC [32–104ºF] | |
Relative Humidity | 0–90%, non-condensing |